System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
37
PLR may be triggered manually from the SC300 web interface, automatically from a Smart Alarm,
or remotely from EDREM or a similar application.
To enable PLR
Use the SC300 keypad to go to: Control Processes > Peak Load Reduction.
Or, in DCTools/Web go to: Control Processes > Peak Load Reduction
Set Enable to Enabled.
Set Maximum Duration and Low Voltage Limit as required.
To manually trigger PLR
Use the SC300 keypad to go to: Control Processes > Peak Load Reduction.
Or, in DCTools/Web go to: Control Processes > Peak Load Reduction
Set Scheduled Start Time and Scheduled Duration as required.
To use a Smart Alarm to activate Peak Load Reduction (optional)
In DCTools/Web go to: Alarms > Smart Alarms
Configure a Smart Alarm with the appropriate trigger conditions for PLR. Note the Smart
Alarm number.
Go to: Control Processes > Peak Load Reduction
Set Activating Smart Alarm to the appropriate Smart Alarm number.