System Operation
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
37
PLR may be triggered manually from the SC300 web interface, automatically from a Smart Alarm,
or remotely from EDREM or a similar application.
► To enable PLR
• Use the SC300 keypad to go to: Control Processes > Peak Load Reduction.
• Or, in DCTools/Web go to: Control Processes > Peak Load Reduction
• Set Enable to Enabled.
• Set Maximum Duration and Low Voltage Limit as required.
► To manually trigger PLR
• Use the SC300 keypad to go to: Control Processes > Peak Load Reduction.
• Or, in DCTools/Web go to: Control Processes > Peak Load Reduction
• Set Scheduled Start Time and Scheduled Duration as required.
► To use a Smart Alarm to activate Peak Load Reduction (optional)
• In DCTools/Web go to: Alarms > Smart Alarms
• Configure a Smart Alarm with the appropriate trigger conditions for PLR. Note the Smart
Alarm number.
• Go to: Control Processes > Peak Load Reduction
• Set Activating Smart Alarm to the appropriate Smart Alarm number.