EasyManua.ls Logo

Eaton SC300 - Page 50

Eaton SC300
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SC300 Handbook
44
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
Manual Rectifier Shutdown
To shut down a rectifier
In DCTools/Web go to: Rectifiers > Configuration.
Set Shutdown to Manual.
In the Rectifiers table click Shutdown. This box only appears when Shutdown is set to Manual.
The rectifier will shut down and the yellow LED will be on.
This function will normally only be used for testing purposes. When the testing is complete, set
Shutdown back to its previous setting (Disabled or Automatic).
Rectifier Restart
To restart all shutdown rectifiers
Use the SC300 keypad to go to: Rectifiers > Rect. Settings (tab) > Restart All Rectifiers.
Or, in DCTools/Web go to: Rectifiers. Click Restart All.
To restart individual rectifiers
In DCTools/Web go to: Rectifiers.
For each rectifier click Startup.
The rectifier(s) will then resume normal operation.
The SC300 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has
failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is set to Disabled,
or Rectifier Shutdown is set to Automatic.

Table of Contents