SC300 Handbook
84
Copyright © 2007-2018 Eaton Corporation. All Rights Reserved.
IPN 997-00012-03 B2 Issue B2 July 2018
Solar Current The total current produced by Solar Chargers
controlled by the SC300.
Only visible if there are Solar Chargers present.
Alternative
Source Current
The total current measured by all analog inputs
configured as Function = Alternative Energy Source
Current, plus the total current of all solar chargers
controlled by the SC300.
Only visible if there are Alternative Energy Sources
present.
Sum of Reported
Rectifier Currents
The sum of the currents reported by all rectifiers.
Where there is no analog input configured as Rectifier
Current, this will be the same value as Rectifier
Current.
Load Power The power being supplied to the load. Load Current x
Bus Voltage.
System Power The output power of the system as a percentage of
the total nominal power of the registered rectifiers.
Solar Power The total power produced by all solar chargers
controlled by the SC300.
Only visible if there are Solar Chargers present.
Phase 1 The AC input phase 1 voltage
Only visible if the SC300 is measuring ac input phases.
Refer to Phase Detection on page 43.
Phase 2 The AC input phase 2 voltage
Only visible if the SC300 is measuring ac input phases.
Refer to Phase Detection on page 43.
Phase 3 The AC input phase 3 voltage
Only visible if the SC300 is measuring ac input phases.
Refer to Phase Detection on page 43.
AC Voltage The average of the ac voltage measured by single-
phase rectifiers.
Or, if 3-phase rectifiers are fitted then the average of
the ac phase voltages is shown.
Highest Rectifier
Heatsink
Temperature
The highest temperature reported by any rectifier.
Fuel level The calculated fuel tank level if Fuel Tank Volume has
been set.
Battery
Temperature
The average of all analog inputs configured as Battery
Temperature.