► To set the DO Control Timeout Period
• On DCTools/web, go to Digital Outputs:
• Set DO Control Timeout Period to the required value. This sets the maximum
time that a digital output will remain in manual control. After that time it reverts
to automatic control.
► To manually control a digital output
Either:
• On DCTools/web, go to Digital Outputs:
• Expand the Digital Outputs table.
• In the Control State column of the required digital output, select Active or Inactive.
• Or, use the SC300 keypad to go to Digital Outputs:
• Select the required digital output. Press Edit.
• Select Active or Inactive. Press Save.
• The DO Manual alarm (if enabled) will activate.
• The corresponding digital output will Energize or De-Energize, as selected in the Active State
column of the Digital Outputs table.
The digital output will revert to Automatic after the DO Control Timeout Period.
While Active or Inactive is selected, the DO will not be operated by any active alarms mapped to
it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.
► To set the state of a digital output from PowerManagerII
• In Web, set the Group of one or more digital outputs to a non-zero value.
Only digital outputs with a non-zero Group are visible in PowerManagerII
• In PowerManagerII select the SiteManager group item.
• Click on the Realtime tab.
• From the drop down list beside the digital output select Active Manual or Inactive Manual.
• The DO Manual alarm (if enabled) will activate.
• The corresponding digital output will Energize or De-Energize, according to its Active State.
While Active Manual or Inactive Manual is selected, the DO will not be operated by any active
alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the
digital output.
► To configure a digital output
1 On DCTools/web, go to Digital Outputs. Expand the Digital Outputs table.
2 Select a Digital Output. Refer to the I/O Board (IOBGP-xx) Connector Pin-outs on page 138 for
IO Board output numbers.
Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules are
connected. See details in the dc power system Installation and Operation Guide.
3 Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.