XS series operating manual 
 
XS user manual v0.55  - 116 - 
IP address 
 
warning 
To set manually a new IP address , the DHCP mode must be OFF ( DHCP = OFF. ) 
 
Select the line ADDRESS IP and validate. 
 
 
Fig 12.8 
  Select the number to be modified by moving the cursor with the RIGHT/LEFT arrow keys. 
  Increase  or  decrease  the  value  with  respectively  the  UP  and  the  DOWN  arrow.  Repeat 
operation for all the numbers if necessary. 
  Enter the new value  with the ENTER key and wait a little time. 
 
Subnet address mask 
warning 
To set manually a new IP address , the DHCP mode must be OFF ( DHCP = OFF. ) 
 
 
 
Fig 12.9 
Proceed exactly as above. 
Protocol and communication port 
  
 The protocol used is TCP/IP 
The software used to control a XS unit must use the port TCP 2001 
 
Syntax rules 
 
The end of a message must be the LF character (hexadecimal 0A, decimal 10). 
The separators inside a message are ; or : 
The commands can be sent either in small letters or in capital letters.