XS series operating manual 
 
XS user manual v0.55  - 135 - 
Measurements on cables 
 
The measurement on cables is similar to the measurement on capacitors 
The measurement configurations on cables are very varied. The measurements have to be performed 
either between each conductor for multi-wires cables, either between main conductor and shielding for 
shielded cables, either between the cable and its environment for mono-wire cables. 
A)  In  that  last  case,  the  generally  used  way  is  to  immerse  the  cable  reel  in  a  water  tank  (called 
SWIMMING POOL), to wait for the water penetration in to the cable reel center, and then to perform 
the insulation resistance between the cable and the water. For safety and construction reasons the 
water  tank  is  grounded.  The  insulation  resistance  measurement  unit  must  be  able  to  measure  a 
specimen with one  grounded end. The units of the MG series allow performing easily this type of 
measurement, because the hot point of the high voltage generator is already grounded. You just have 
to connect the measurement input of the unit (with the HV probe) on the cable to be measured and to 
trigger the measurement. 
 
B)  Another  specific  point,  when  measuring  on  cables,  is  that  the  specifications  of  the  cable 
manufacturers give resistance values for a standard length of cable equal to 1 km (1000 meters). 
When  testing  the  reels  of  cable,  those  are  never  equal  to  the  standard  length,  that  forces  the 
operators to calculate the resistance as  a function of the cable length and the number of wires in 
parallel for the multi-wires cables. Consequently the built-in comparators of the measurement units 
can not be used, because they compare regarding to the total insulation value and not regarding the 
standard value. The units of the MG series allow with the option 23 to display insulation resistance 
measurements reduced to 1 km and 1 wire, and therefore allow the use of the built-in comparators. 
The operator can enter in a specific menu of the unit the length of the cable under test as well as the 
number of wires. The result is given in Mohm per km. 
i.e. : the unit measures a value of 10 Mohms for a 10 km long mono-wire cable. Therefore, the value 
reduced to 1 km will be : 
(Rtotale / 1 km) x Length = 100 Mohm.km 
For the same cable with 10 wires, the value for 1 wire will be : 
100 Mohm.km x 10 = 1000 Mohm.km 
 
C) The  insulation resistance value  of  a  cable being a function following  a time  exponential  law, it  is 
important to make sense to the measured value, to indicate the duration of the measurement. The 
units of the MG series allow complying with this requirement with the built-in timer, able to measure 
times going from 1 second up to 16 minutes.  
 
Measurement voltage selection 
 
The insulation resistance measurements intending to verify that materials or  equipments comply with 
standard requirements, it is important to refer to these standards to select the voltage. The standard 
voltages are generally : 50, 100, 250, 500 VDC. 
In case of no standard, select a 100 VDC value. 
When measuring on  capacitive specimens and when studying the  voltage influence on the insulation 
resistance  values,  it  is  important  to  start  always  with  the  lowest  voltage  and  then  to  follow  the 
measurements in increasing the voltage. A procedure in the reverse way could give incoherent results.