TABLE 3-1 Factory Defaults, Optional Settings and Ranges
Parameter
Special Criteria Default Optional Settings/Ranges Units
LO ALRM All All OFF ON
HI ALRM All All OFF ON
-P, -T, -U, -F
DPCONVERT=NO
DPCONVERT=YES iWG [Pa] None
ALRM UM=FPM [m/s] 0 to 999999 [0.00 to 99.99] FPM [m/s]
ALRM UM=CFM [L/s] 0 to 999999 [0 to 999999] CFM [L/s]
ALRM UM=FPM [m/s]
0 to 999999 [0.00 to 99.99]
(± if DIRECTION=BI)
FPM [m/s]
ALRM UM=CFM [L/s]
0 to 999999 [0 to 999999]
(± if DIRECTION=BI)
CFM [L/s]
ALRM UM=iWG [Pa]
0.00 to 5.00 [0 to 1250]
(± if DIRECTION=BI)
iWG [Pa]
TOL All All 15% > of 5% or 20 FPM [0.10 m/s] TO 100%
DELAY All All 2min 0min to 15min
-P, -T, -U, -F
DPCONVERT=NO
DPCONVERT=YES N/A N/A
RESET All All AUTO MANUAL
FAN ALRM Advantage IV -F/An OFF MIN, DEV, %MAX
ON ALRM Advantage IV -F/An KEEP IGNR
ALRM UM Advantage IV -F/An FA TYPE=MIN FPM [m/s] CFM [L/s]
%MAX
25% 10% to 100%
FA TYPE=MIN
ALRM UM=FPM [m/s]
0 to 999999 [0.00 to 99.99] FPM [m/s]
FA TYPE=MIN
ALRM UM=CFM [L/s]
0 to 999999 [0 to 999999] CFM [L/s]
DELAY Advantage IV -F/An 2min 0min to 15min
ZERO OFF Advantage IV -F/An YES NO
RESET Advantage IV -F/An AUTO MANUAL
R1 ASGN EB-Flow2 All NONE ALRM or TRBL
R1 STATUS EB-Flow2 All NO NC
ALRM UM
12
All
SETPNT Advantage IV -F/An
0
-P, -T, -U, -F
0
-B
ZERO OFF All
YES
FPM [m/s] CFM [L/s]
-B
Note 12: The default and only option for ALRM UM is FPM [m/s] when the AREA parameter is set to 0 or {null}.
SETPNT All
-B
NO
SettingsMenu_r1p Table 3-1 - Page 5