Firmware V6.6.9
29.07.2020
141/147
•
•
•
System centre SIOX extension module
Other interfaces Power supply for external SIOX
Environmental conditions
Transport and storage
The controller contains a 3 V lithium cell (design type
CRC 2450 N, shelf life 10 years) with capacity of 540
mAh and lithium content of 0.16 g.
The battery complies with the UN3090 requirements
for lithium metal cells. No special markings or
measures for transport and storage are required up to
alithiumamountof2.5kgperpackage(totalamount
for pallets or containers).
-
Weight approx. 1600 g approx. 800 g
Temperature range Transport: -20 °C ... +80 °C
Operation: 0 °C ... +50 °C
Temperature change Transport: max. 20 K/h
Operation: max. 10 K/h
Relative humidity
(non-condensing)
Transport: 8% ... 80%
Operation: 20 % ... 80%
Shock
according to DIN EN
60068-2-27
Transport and operation: 30 g
Vibration 10 Hz... 150 Hz
according to DIN EN
60068-2-6
Transport and operation: 2 g
Atmospheric pressure Transport: 660 hPa ... 1060 hPa
Operation: 860 hPa ... 1060 hPa
Standards and Directives
Protection rating IP20 (EN 60529)
CE conformity according to
(see
https://edp.eckelmann.de/
edp/lds/_aftpgg7so5)
Low Voltage Directive 2014/35/EU;
Official Journal of the EU L96, 29/03/2014, pages 357-374
EMC Directive 2014/30/EU;
Official Journal of the EU L96, 29/03/2014, pages 79-106
RoHS Directive 2011/65/EU;
Official Journal of the EU L174, 01/07/2011, pages 88-11
12.2 Mechanical data
•
•
•
1)
Warning about dangerous electrical voltage! Danger of electric shock! BEFORE connection, it
must be checked that no voltage is present at the 230 V AC digital inputs and 230 V AC relay
outputs! Low voltage and safety extra-low voltage must not be applied together at the digital inputs A1/
A2 and B1/B2 and the relay outputs 15/16/18, 25/26/28 and 35/36/38! Rating data of the insulation of
the outer power circuits:
Rated insulation voltage: 300 V AC
Test voltage (L to PE): 1500 V AC
Safe electrical isolation
Impact loads on the touch screen are not permitted!