EasyManua.ls Logo

ECKELMANN CI 4000 Series - SIOX - Connection of Energy, Gas, Water, Event Meters

ECKELMANN CI 4000 Series
147 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V6.6.9
29.07.2020
45/147
1.
2.
3.
No. Function
1 Currently has no function
2 Currently has no function
3
Not jumpered = factory settings (open): The position of a manual control switch acts directly on the
associated relay (ON/OFF/AUTOMATIC): the relays can be overridden manually.
Jumpered: For special functions, the position of a manual control switch has no effects on the associated
relay: only the controller can switch the relay.
For details about the position of the manual control switch, see chapter SIOX manual / automatic mode
selection
6.2.3 SIOX - connection of energy, gas, water and event meters
OnlymetersanddialswithS0interfacearesupported(reedcontactor24VDCtransistoroutput).In
comparison with meters with reed contact (universal meter), attention must be paid to their polarity when
connectingmeterswithtransistoroutput.A24VDCpowersupplyisneededforthepowersupplyoftheS0
interface.
Configuration of meter and transformer constant (Menu 4-1-6):
Meter constant (pulses per kWh or m
3
)
Transformer constant (conversion ratio of current transformer)
Unit (unit of measure) (kWh or m
3)
For further details, see chapter Calculation of consumption / power from meter values.
Connection and wiring examples for energy, gas and water meters with a SIOX extension module:
Warning about dangerous electrical voltage! Attention: external voltage! The configuration of the
jumpers must always be performed when no voltage is present and with the connectors at the inputs
(terminals A1, A2/ ... /L1, L2) detached as a voltage of 230 V AC can be present at these terminals
under certain circumstances!
The digital inputs needed for this must be configured as 24 V DC/AC inputs using jumpers; see chapter
SIOX - configuration of the jumpers.
When using electronic meters, the settings with regard to their meter and transformer constants must
be taken into account, otherwise the controller produces incorrect energy evaluation due to incorrect
meter and transformer relationships!

Table of Contents

Related product manuals