The following switch positions are possible:
A: Automatic ON (default switch position)
If any switch is in the A position, the controller registers the logical AUTOMATIC OPERATION state:
Theconnectedequipmentiscontrolledas the software envisages (normal operation).
O: Manual OFF
If any switch is in the 0 position, the controller registers the logical MANUAL OPERATION OFF state:
The connected equipment is not controlled - even if the software envisages this
, e.g. light remains off continuously!
I: Manual ON
If any switch is in the I position, the controller registers the logical MANUAL OPERATION ON state:
The connected equipment is always controlled - even if the software does not envisage this
, e.g. light remains on continuously!
6.2.5 SIOX - Status LEDs
The "I: Manual OFF" and "I: Manual ON" positions override the state desired by the controller! A
message is generated if the Manual OFF and Manual ON manual control switches are operated.
SIOX extension modules without manual control switches do not have this function!
Warning about dangerous electrical voltage! Danger of electric shock! The device must never be
operated without its case. Before opening the case, the device must be disconnected from the power
supply