5 Function of System Centre
5.1 Starting Characteristics
The following are distinguished for any start-up of the controller:
First start - Reset System
Restart - Restart of the controller
5.1.1 First start - Reset System
Reset to delivery condition (factory settings), see Menu 4-1-11 - Reset System:
All data will be completely removed from the system!
The system centre will be restarted twice
5.1.2 Restart - Restart of the controller
For a restart, the device is restarted with all configured parameters. A restart can be initiated using the following
procedure:
Menu 4-1-11 - Reset Systemor
disconnectionandreconnectionofthepowersupply,seechapterSwitching on system centre.
5.2 Configuration of the E*LDS system using the LDSWin PC software
The system centre and all components connected to it can be conveniently configured using a PC with the
LDSWin PC software. This also includes the possibility to read out the configurations of all components and
store them on the PC ("Save parameter sets" function). Thus, in the case of any required replacement of a
component, the configuration can be written back to the replacement device. Further information for this can be
found in the LDSWin operating instruction.
For local configuration, the system centre is connected via null modem cable (EAG No. PCZKABSER2) to the
PC/laptop.
In addition, for the purpose of remote adjustment and maintenance, the system centre can also be operated
using a PC via a modem and via a network. The system centre can be used for the storage of store-specific
data from LDSWin so that the same layout can be used for different LDSWin installations.
A configurable TCP/IP port is used for the communication with LDSWIN. This can be freely selected from the
range of free ports (1024 - 65535) in accordance with the network conditions. As standard, LDSWin uses the
port 5000: 192.168.161.66:5000 (see menu 4-1-5).
Risk of loss of data and the configuration! All saved data and configurations of the system centre
are irrevocably lost during deletion of the archives (operating and energy data), the alarm and
message list as well as during reset to factory settings!
For more details, see chapter Configuration of the E*LDS system with service PC locally, page 44
Configuration of the E*LDS system using Service PC locally. The operating manual for the LDSWin PC
sofware can be found in E°EDP.