Note: In the example here, the first relay output of the SIOX extension module is used as a defrost timer for a
case controller. For further details about the configuration of the SIOX, see chapter SIOX - connection to the
system centre.
Relay output
Terminal No. Function
Changeover contacts
Without switch * With switch *
1
16, 18, 15
Week timers
(e.g. for defrosting, lighting, car park lighting)
or
for load shedding
2
26, 28, 25
3
36, 38, 35
4
46, 48, 45
Normally open contacts
Without switch * With switch *
5
53, 54
13, 14
6
63, 64
23, 24
7
73, 74
33, 34
8
83, 84
43, 44
* COMBICON terminal blocks of the extension modules
Without switch
- Changeover contacts: 4 x 3-position COMBICON terminal blocks
4x
- Normally open contacts: 4 x 2-position COMBICON terminal blocks
4x
With switch
- Changeover contacts: 1 x 12-position COMBICON terminal block
1x
- Normally open contacts: 1 x 8-position COMBICON terminal block
1x
•
•
In order to fuse the supply line and relay outputs, a circuit breaker with the following characteristics
must be used for each relay output:
Rated current for 230 V AC: 6(3) a
Tripping characteristic (typical): B