EN_
810G20 - Version V5 Juillet 2020 P. 60
Traduction de la notice originale
To program a cycle with recovery, select 1. To program a cycle without
recovery, select 0.
By default, the pressure control duration is 2 minutes.
To modify, enter the value, and press ENTER to confirm.
NB: This screen appears only if recovery was previously selected.
To program a vacuum, select 1. If not, select 0.
Enter the required duration of vacuum.
NB: This screen appears only if vacuum was previously selected.
Enter the required leak test duration.
NB: This screen appears only if vacuum was previously selected.
To program a refrigerant charge, select 1. If not, select 0.
To ensure charge speed and accuracy it is unconditionally required to perform charge directly after
vacuum.
To modify the quantity, input the amount and press ENTER to confirm.
Press ENTER to start the programmed cycle.
Cycle sequence: Refer to chapter 9.22. Cycle Sequence
9.1.1. Refrigerant recovery
With this function, the operator empties the ECS circuit before to repair/maintain it.
From the >> ECS OPERATION << menu, select 1.
Recovering
1. Yes
0. No
Recovering
Pressure control
≥ min
Vacuum
1. Yes
0. No
Vacuum duration
≥0 min
Tightness check
µ min
Refrigerant charge
1. Yes
0. No
Charge qty
0 g
Start process
ENTER: Yes
STOP: No
>> ECS OPERATION <<
1.New operation
2.Refrig transfer