EN_
810G20 - Version V5 – Juillet 2020 P. 75
Traduction de la notice originale
12. Services Menu
12.1. Degassing of non-condensable
This task de-gasses and purges the non-condensable gas in the internal refrigerant tank.
From the homepage, access the menu by pressing ENTER.
The screen displays the pressure in the unit’s refrigerant tank.
To de-gas, press ENTER: The unit will open the de-gassing solenoid valve
for 2 seconds.
To exit this menu, press STOP.
12.2. Scale sensors
This menu shows the values of the unit's scales sensors.
From the homepage, access the menu by pressing ENTER.
The screen displays the quantities measured by the scales for:
• Refrigerant (Internal tank)
• Recovered oil
To exit this menu, press STOP.
>> MAIN MENU <<
1.ECS Operation
2.History
3.Settings
4.Tools ã
>> TOOLS <<
1.Uncondensable vent
2.Weighing sensors
3.Pressure sensors
TANK AIR PURGE
Tank 11.1 bar
ENTER: Yes
STOP: No
>> MAIN MENU <<
1.ECS Operation
2.History
3.Settings
4.Tools ã
>> TOOLS <<
1.Uncondensable vent
2.Weighing sensors
3.Pressure sensors
Tank 8483 g
Waste oil 14 g