Chapter 1: Introduction
14 P/N 3102309-EN • REV 001 • ISS 18JUL19
Command button Minimum fire
privilege level
Description
Maintenance Not
Clean
0 Maintenance (not clean) report. Lists all addressable smoke
detectors that have a %Dirty value of 80% and greater. Smoke
detectors that are more than 80% dirty should be cleaned or
replaced as soon as possible.
Maintenance
(device)
0 Maintenance report. Lists the %Dirty value for a selected detector
on a signaling line circuit. The report includes the detector’s model
type, primary and alternate alarm sensitivity value, and, if
programmed, a location description.
Revision 0 Revision report. Creates a report that lists the revision level of all
the hardware and software components installed in a node
selected in the project tree.
1 Hour Access 0 Provides a validation code that unblocks the Remote Write
command for one hour to permit database changes. The code
must be entered in the 4-CU to allow database downloads from a
programming computer to the 4-CPU in the EST4 control unit.
When tapped, the operator alert sounds and the Other command
button displays to show the “Remote write unlocked” local monitor
event.
8 Hour Access 0 Provides a validation code that unblocks the Remote Write
command for eight hours to permit database changes. The code
must be entered in the 4-CU to allow database downloads from a
programming computer to the 4-CPU in the EST4 control unit.
When tapped, the operator alert sounds and the Other command
button displays to show the “Remote write unlocked” local monitor
event.
Cancel Access 0 Immediately restores the Remote Write command and prevents
access to database changes.
Reset 0 Resets the local control unit. When tapped, the Reset control
button indicator flashes.
Reset All 0 Resets all networked nodes. When tapped, the Reset control
button indicator flashes.
Test Indicators 0 Activates a test of all control unit LEDs and installed control-
display module LEDs.
Status Holdup 1 Future feature.
Lock Incoming
Network
1 Blocks web services for all 4-FWAL series nodes.
Unlock Incoming
Network
1 Unblocks web services for all 4-FWAL series nodes.
Freeze History 3
Archives the most recent events (up to 10,000 events) so that they
cannot be overwritten.
Toggle Alternate
Sensing
3 Switches detector alarm sensitivity levels from primary to alternate
or from alternate to primary, whichever is currently active.
Set Date Time 3 Opens a keypad that lets you set the system time and date.
Enable 3 Enables a device selected in the project tree.
Disable 3 Disables a device selected on the project tree.
Activate 3 Activates AND groups and command lists selected in the project
tree.
Restore 3 Restores AND groups the command lists.
On 3 Activates input and output devices selected in the project tree.