Chapter 2: Basic operating instructions
P/N 3102309-EN • REV 001 • ISS 18JUL19 23
To activate a lamp test:
1. Press the Lamp Test operator control button, if available
or
Press a control-display button programmed to activate the lamp test.
2. If prompted, enter the fire privilege PIN using the interactive keypad.
Activating an alarm signals drill
The EST4 drill feature lets you activate alarm signals manually without putting the control unit into alarm. When
you activate a drill, all audible alarm signals turn on and, if configured, all visual alarm signals, but other automatic
fire alarm responses are not activated. The alarm signals remain active until the drill is canceled.
You can activate a drill using an operator control button, when programmed as Fire Drill, or a control-display
module button programmed to activate the drill.
Note: The drill function can be programmed for a fire privilege PIN. The default setting is no PIN required.
To activate a drill:
1. Press the Fire Drill operator control button if available
or
Press a control-display button programmed to activate the drill.
2. If prompted, enter the fire privilege PIN using the interactive keypad.
Note: To cancel the drill, press the button a second time.
Resetting the life safety system
WARNING: Death or serious injury. The protected premises may be occupied. Do not reset the fire alarm system
until the proper authorities have determined that the threat of fire is no longer present.
Resetting the life safety system restores the system to its normal state, provided all latched inputs have been
restored before the end of the reset cycle.
Notes
The Reset button may be inoperable for up to three minutes following the first alarm event.
The Reset button does not affect disabled points or manually overridden functions.
The reset function can be programmed for a fire privilege PIN. The default setting is no PIN required.
To reset the life safety system:
1. Press the Reset operator control button.
2. If prompted, enter the fire privilege PIN using the interactive keypad.