Beeps while primary source
is interrupted
Alarm on (default) Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default) Bypass enable
25 Record Fault code
Record enable (default) Record disable
26
Bulk charging voltage
(C.V voltage)
default: 56.4V
If self-defined is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
61.0V. Increment of each click is
0.1V.
27 Floating charging voltage
default: 54.0V
If self-defined is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
61.0V. Increment of each click is
0.1V.
28
AC output mode
*This setting is only
available when the inverter
is in standby mode (power
Switch in off position).
Single: This inverter is used
in single phase application.
Parallel: This inverter is operated in
parallel system.
When the inverter is operation in split phase application, set up
inverter to be operated in specific phase.