Parameter Description Min Max M.U.
CP17 Maximum hours of use for compressor 0 6500 Hours*10
The hours of use of each single compressor can be reset from the State menu.
Selecting/deselecting compressors
Each individual compressor can be selected from the State menu. Deselection of a compressor entails the following:
The compressor availability is set to zero
Zero setting of all its possible alarms
Its alarms are not managed
Compressor block
Management of this alarm applies both to step compressors and to compressors with continuous regulation and is
active if the compressor is selected. The activation of this alarm blocks the compressors in use. In the case of step
compressors, the availability of another compressor is checked at the same time as the compressor block. If it is
available it will be selected depending on the policy (CP10) and immediately switched on.
CONDENSATION CONTROL
The device can be configured to manage an inverter fan or one or more homogenous digital fans (max. 4) by setting
parameter Fn25:
Parameter Description Min
Max
M.U Notes
Fn25 Number of fans per step for fan coil -1 4 Num
-1 = no condensation.
0 = continuous fan.
>0 = Fn25 represents the number of
digital fans.