49
Fans thermal switch
The intervention of the digital fan thermal protection is blocked for the correctly used fan.
If another fan is available it will be selected depending on the policy (Fn11) and immediately activated. The
contemporaneous intervention of the thermal protections of all of the digital fans causes an alarm which blocks the
machine.
In the case of fans with continuous control or digital fans in which a single common thermal fan has been configured,
the tripping of the thermal switch causes the machine to shut down.
ADVANCED FUNCTIONS
On/off device
The activation/deactivation of the device used for controlling resources may be carried out via keyboard or digital
input:
ON/OFF from keyboard: The device may be switched on or off using the keyboard from the Folder
Programming menu OP. This function is not active if the ON/OFF is configured via digital input (e.g. for DI5,
CF20=13). In OFF mode, the screen will display the word OFF.
ON/OFF via Digital Input: If a digital or analogue input is configured for this function, the device state
depends on the input state. In OFF mode, the word OFF will flash on-screen. ON/OFF via keyboard is not
active.