EMC Connectrix B Series DS-4900B Version 5.1 Hardware Reference Manual
DS-4900B Specifications
Facility requirements
To ensure correct operation of the switch, the facility where the
switch is in use must meet the following requirements:
Electrical:
Primary AC input 100-240 VAC (switch autosenses input
voltage), 47-63 Hz
Correctly wired primary outlet, protected by a circuit breaker
and grounded in accordance with local electrical codes
Adequate supply circuit, line fusing, and wire size, as
specified by the electrical rating on the switch nameplate
Electrical interference must be less than the levels stated in the
standards listed in Table 6-4 on page 6-7, under “Immunity”
Thermal:
Air flows from the nonport side to the port side. A minimum
air flow of 47 cu ft/min (79.8 cu m/hr) available in the
immediate vicinity of the switch
Ambient air temperature must not exceed 40º C (104º F) while
the switch is operating
Environmental: Specifications are listed in Table 6-3 on page 6-6.
Cabinet:
Cabinet space of 2U in a EIA 19-in. cabinet
All equipment in cabinet must be grounded through a reliable
branch circuit connection
The additional weight of the switch must not exceed the
cabinet’s weight limits
The cabinet must be secured to ensure stability in case of
unexpected movement