“MTOWER PLUS” basic settings.
Basic settings are: PASSCODEs, Time & Date, International Units.
Standard settings are: Probes calibration and operating modes (bleed - inhibitor - biocide).
Advanced settings are: Flow meter, Alarm and Option menu.
All these three settings must be set in order to properly operate the instrument.
PASSCODE for “Setup” and “Probe” menu access.
To grant access into “Setup” menu press the wheel from main screen, choose “Setup” and enter the PASSCODE.
If this is the rst time here then the PASSCODE is 0000 (factory preset). Press wheel 5 times to grant access.
Otherwise press the wheel 1 time and enter the PASSCODE. Numbers can be selected by rotating the wheel.
To set a new PASSCODE choose “PASSCODE ” from “Setup” menu and enter a four numbers code. Click on “EXIT”
and choose “YES” to save request. The new PASSCODE is now ready.
To change default PASSCODE for “PROBE” menu, repeat procedure once into that submenu.
Note: both the PASSCODEs are independent!
Lost PASSCODE ?
Please dont’ forget the PASSCODE (if changed). In the unfortunate event, please call your local distributor for unlocking procedure. There is no way for you to
recover lost PASSCODE.