9
“MTOWER PLUS” main screen.
Conductivity status Message Explanation Action Required
“INHIBITOR”
INHIBITOR mode in progress.
Ouput 2-E-N active
Corrosion inhibitor dosage in progress.
No action required.
“BLEED hh:mm”
BLEED hh:mm mode in progress.
Bleed Valve active
Restoring conductivity.
No action required.
“PRE BLEED”
PRE BLEED mode in progress.
Bleed Valve active
Water discharge before dosing biocide.
No action required.
“PRE BIOCIDE 1”
“PRE BIOCIDE 2”
PRE BIOCIDE 1 or 2 in progress
Output 5-E-N or 6-E-N active
Biocide activator dosage in progress.
No action required.
“BIOCIDE 2”
BIOCIDE 2 in progress
Output 4-E-N active
Killing dangerous organism in progress.
No action required.
“LOCKOUT 1”
“LOCKOUT 2”
LOCKOUT 1 or 2 in progress
Bleed Valve disabled
Bleed mode locked after biocide dosage.
No action required.
“BLEED TIMEOUT” Pre-bleed activity time exceeded Check biocide 1 or 2 menu
Alarm status Message Explanation Action Required
“ALARM”
ALARM
Output 10-11-12 active (see contact mode)
Check alarm by rotating wheel in main screen
until to show “Status Alarm”
Once alarm status is xed the instrument will resume interrputed
activities.
Outputs status Message Explanation Action Required
“FEED D1” D1 output active No action required.
“FEED P1” P1 Proportional output active No action required.
“MTOWER PLUS” main display shows more information about plant proper functioning. By rotating wheel clockwise the
instrument will show: “Status Output”, “Status Totalizer”, “Status Level”, “Status Alarm”, “Status Biocide”.
See above table for messages explanation.
“MTOWER PLUS” Operating Status Messages.
Local Date
Local Time
ORP reading
Plant temperature
Conductivity reading pH reading
Outputs status
Alarm status
Conductivity status
Connection Status
LAN Connected - Connected to ERMES
LAN Cable disconnected
LAN Connected - Not connected to ERMES
USB pen-drive connected