Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
65
Section 9: Set-Up Routines
Set-Up Routines
9.1.10 Interlock
The interlock inputs can be used to inhibit the actuator movement in the open or closed
direction. The controls are momentary; the inhibiting action continues while the relevant
signal is present. The interlock controls work when the local selector is in LOCAL or in
REMOTE. The ESD control overrides the interlock controls.
The following options can be congured:
— Interlock OP: active when signal is PRESENT, active when signal is ABSENT,
no action (OFF).
— Interlock CL: active when signal is PRESENT, active when signal is ABSENT,
no action (OFF).
Configuration procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see entering the set-up mode). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "INTERLOCK".
• Press YES if the congured value of the Open Interlock is correct (PRESENT,
ABSENT, OFF). If not, press NO to change it and then press YES.
• Press YES if the congured value of the Close Interlock is correct (PRESENT,
ABSENT, OFF). If not, press NO to change it and then press YES.
9.1.11 2-Speed Timer
The “2-speed timer” routine is used to extend the actuator travelling time in the opening and/
or closing direction, by driving the motor via pulses that results in duration (ON and OFF time)
becoming congurable. Pulsing control can be applied to full travel or only a part of it.
Start position and stop position may be adjusted from 0% - 100% separately in opening and
closing direction.
ON time and OFF time may be adjusted from 1 sec - 200 seconds separately in both the
opening and closing direction.
Figure 63
Motor
Start
position %
Stop
position %
On
time
On
time
On
time
Off
time
Off
time
Off
time