October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
58
Section 9: Set-Up Routines
Set-Up Routines
LED colors
• Press YES if the color of the open LED is correct. Press NO to change it, and then
press YES to conrm.
• Press YES if the color of the close LED is correct. Press NO to change it, and then
press YES to conrm.
• Press YES if the color of the alarm LED is correct. Press NO to change it, and then
press YES to conrm.
9.1.6 Output Relays
Monitor relay
The voltage-free, change-over contacts of the monitor relay indicate that the actuator
is either available for remote control or that a problem or a condition preventing remote
control of the valve exists.
The monitor relay is normally energized and will be de-energized on:
• mains voltage failure
• lost phase
• internal temperature alarm
• K1 contactor failure
• K2 contactor failure
• position sensor failure
• speed sensor failure
• conguration error
• hardware error
• mid-travel alarm
The following situations can be congured individually to not de-energize the monitor relay
when they occur:
• motor over-temperature
• over-torque
• jammed valve
• LOCAL/OFF selected
• manual operation
• ESD signal on (ESD-EFS)
• low lithium battery (if present)
• LOCAL/STOP pressed