Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
69
Section 9: Set-Up Routines
Set-Up Routines
9.1.13.4 Torque Bypass (%)
Since a momentary high torque may be required to unseat certain valves, the torque
bypass routine disables the torque alarm when an open or close command is received and
the actuator is fully open or closed. The torque bypass is expressed as a % of position and is
congurable from 0% to 20%. For example: if a 10% bypass value is set, we may have:
bypass active in Opening: from 0% to 10%
bypass active in Closing: from 100% to 90%
To disable torque bypass, congure 0%.
Configuration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "Miscellaneous".
Press NO to scroll the list of routines and press YES to select "Torque Bypass".
Press YES if the setting is correct; otherwise, press NO to change. Press YES when
the value is correct.
9.1.13.5 Valve Jammed (Time)
The valve jammed time is used to monitor the following situations:
1. The time passed after receiving an open or close control is greater than the “valve
jammed time,” but the variation in valve position is smaller than 0.5%. The motor is
stopped, the command is cleared and a “valve jammed” alarm indication is generated.
2. The valve is moving, but during valve travel the variation in valve position is smaller
than 0.5% of the time equal to “valve jammed time”. The motor is stopped, the
command is cleared and a “mid-travel alarm” indication is generated.
The valve jammed time is expressed in seconds and can be congured from 0 to 100
seconds. Congure “0” to disable the routine.
Configuration procedure
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and enter the password according to the instructions
(see “Entering the set-up mode”.) When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "Miscellaneous".
Press NO to scroll the list of routines and press YES to select "Valve Jammed".
Press YES if the setting is correct; otherwise, press NO to change. Press YES when the
value is correct.

Table of Contents

Other manuals for Emerson Bettis XTE3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Bettis XTE3000 and is the answer not in the manual?

Emerson Bettis XTE3000 Specifications

General IconGeneral
BrandEmerson
ModelBettis XTE3000
CategoryController
LanguageEnglish

Related product manuals