temperatures (>40° C or >104° F) and drive operation near the
maximum speeds.
Transformer output voltage drop may become a limiting factor
at motor speeds and loads near maximum ratings. Typically,
higher KVA transformers have lower voltage drop due to lower
impedance.
Drive/Motor Combination Suggested KVA Rating
Eb-202/NT-207 1.0
Eb-203/NT-207 1.0
Eb-202/NT-212 1.2
Eb-203/NT-212 1.7
Eb-203/MG-316 2.3
Eb-205 / MG-340 3.0