Chapter 5 iCOM Controller 45
Liebert. PEX+Series Precision Air Conditioner User Manual
5.7.9 OPTIONS SETUP
The OPTIONS SETUP menu is used to set the parameters according to the equipment-specific demands. See Table
5-29 for detailed descriptions.
Table 5-29 Descriptions of OPTIONS SETUP parameters
Auto, 1
(compressor 1
being the
primary one), 2
(compressor 2
being the
primary one)
Compressor sequence. Range: Auto, 1 (compressor 1 being the
primary one), 2 (compressor 2 being the primary one)
Hot water heating enabled
LWD connected. Range: Yes (water low sensor connected), No
(water low sensor not connected)
Humidifier Bottle Flush Time
Humidifier Bottle Manual Flush
Dehumidification enabled.
Dehumidification Fan Control Enabled
On-off key enabled. If ānoā is selected, the ON/OFF key cannot be
used to perform on/off operation on the machine.
Cooling water auto flush time, unit: hr (hour)
Free cooling auto flush time, unit: hr (hour)
5.7.10 SERVICE INFO
The SERVICE INFO menu provides the contact information of maintenance personnel. The maintenance personnel
can input and save their contact information through this submenu.