The ROC800 provides terminations for a four-wire 100-ohm platinum
RTD with a DIN 43760 curve. The RTD module supports RTDs with
alphas equal to 0.00385 or 0.00392 //C. You can use a two-wire or
three-wire RTD probe instead of a four-wire probe, but they may
produce measurement errors due to signal loss on the wiring.
Wiring between the RTD probe and the ROC800 must be shielded wire,
with the shield grounded only at one end to prevent ground loops.
Ground loops cause RTD input signal errors.