ROC800-Series Instruction Manual
7-2 Calibration Revised July-2017
Establishing verification and calibration routines ensures not only that
your devices and software are functioning optimally but that your
organization is in compliance with appropriate industry and
governmental requirements.
7.3 Preparing for Calibration
Before calibrating the inputs from a sensor, HART device, or other
device, you should prepare the ROC800.
1. Verify the inputs are correctly wired. For information on wiring the
inputs, refer to Chapter 4, Input/Output Modules.
2. If you are calibrating a pressure sensor input, be sure to remove the
sensor from the flow as directed in the calibration procedure in the
ROCLINK 800 Configuration Software User Manual (for ROC800-
Series) (part D301250X012)or the ROCLINK 800 Configuration
Software User Manual (for ROC800L) (part D301246X012).
3. Verify that you have connected any external monitoring devices
(such as multimeters) to the ROC800, if they are required for the
calibration.