To restore the ROC800 to factory defaults (that is, as the ROC800
was delivered to you from the factory without installed user programs,
FLASH memory contents, FSTs, DS800 applications, or
configurations) without connecting to ROCLINK 800, use this
procedure:
1. Remove power from the ROC800.
2. Press and hold the RESET button on the CPU.
Note: Use a small screwdriver or a straightened paper clip to press
the RESET button.
3. While holding down the RESET button, restore power to the
ROC800.
4. Wait 3-5 seconds and release the RESET button.
Note: If none of these methods solves the problem, contact your local
sales representative.
6.2.4 Powering Up
If you are experiencing trouble with powering up the ROC800:
Check the wiring connections at terminations on the Power Input
module and the wiring at the power source.
Check the internal battery for voltage. Refer to Chapter 3, Power
Connections.
Check the external batteries, if applicable, for voltage.
Note: If none of these methods solves the problem, contact your local
sales representative.
6.2.5 MVS or MVS I/O Module
If you are experiencing trouble with the MVS or MVS I/O module:
If more than one module is connected to the ROC800, use the
ROCKLINK 800 Configuration software to ensure that each module
has a unique address.
Reset the module back to factory defaults. Refer to the ROCLINK 800
Configuration Software User Manual (for ROC800-Series) (part
D301250X012) or the ROCLINK 800 Configuration Software User
Manual (for ROC800L) (part D301246X012).
Note: If you believe an MVS or MVS I/O module is damaged or faulty,
contact your sales representative for repair or replacement.