EasyManuals Logo

Emerson ROC827 User Manual

Emerson ROC827
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
ROC800-Series Instruction Manual
Revised July-2017 Power Connections 3-23
Table 3-16. Power Consumption of the APM Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
APM Module
110 mA @ 12 volts dc
1300 mW
1
Power provided by the
module’s +T port
1.25
*
Measured
Current Draw (from +T
port in mA) * 24
1
Table Total
Table 3-17. Power Consumption of the RTD Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
RTD Module
65 mA @ 13.25 volts dc
1
Table Total
Duty Cycle
An RTD has no associated duty cycle. Consequently, always set “1”
as the duty cycle value.
Table 3-18. Power Consumption of the Thermocouple Module
I/O Module
Power Consumption (mW)
Quantity
Used
Duty
Cycle
Sub-Total
(mW)
Description
P
TYPICAL
Thermocouple Module
84 mA @ 12 volts dc
1008 mW
1
Table Total
Note: The Series 1 CPU does not support the TC2 module.
Duty Cycle
A thermocouple has no associated duty cycle. Consequently, always
set “1” as the duty cycle value.