5.4 Engineering Assistant communication
troubleshooting
Table 5-3 identifies the most common communication issues between the Engineering
Assistant software and the Rosemount 3051SMV.
Table 5-3: Corrective Action for Engineering Assistant Communication Problems
Symptom Corrective action
No Communication
between the
Engineering Assistant
software and the
Rosemount 3051SMV
Loop wiring (HART)
HART protocol communication requires a loop resistance value
between 250 to 1321 ohms, inclusive.
Check for adequate voltage to the transmitter. See Load limitations.
Check for intermittent shorts, open circuits, and multiple grounds.
Check for capacitance across the load resistor. Capacitance should be
less than 0.1 microfarad.
Engineering Assistant
Verify correct COM port selected.
Verify laptop computer is not in low energy mode (certain laptops
disable all COM ports in low energy mode).
Check if HART modem is properly connected.
Check if HART driver is loaded and installed. If using a HART USB port
modem, install drivers from CD-ROM provided with USB modem.
Check if another HART configuration program, such as AMS Device
Manager, is currently open. Only one HART configuration program
may be opened at a time.
Verify the COM port buffer setting is set to the lowest setting (1) in
the advanced COM port settings and re-boot the computer.
Set the Device Address to search All.
5.5 Measurement troubleshooting
The transmitter provides a means to display the current process variables and flow
calculations. If the process variable reading is unexpected, this section provides the
symptoms and possible corrective actions.
Table 5-4: Unexpected Process Variable (PV) Readings
Symptom Corrective action
High PV Reading Primary element
Check for restrictions at the primary element.
Check the installation and condition of the primary element.
Note any changes in process fluid properties that may affect output.
Impulse piping
Reference Manual Troubleshooting
00809-0100-4803 October 2018
Emerson.com/Rosemount 137