3. Select the Custom Liquid (Density [T]) option.
4. Enter the Nominal and Operating Temperature Range. Engineering Assistant will
use this range to identify the temperature values at which the fluid properties are
required.
5. Select Next to continue the flow configuration on the Fluid Properties tab.
6. Enter the Custom Liquid Density at the given temperatures.
Note
All temperature values may be edited except the minimum and maximum
temperatures.
7. Enter the Reference Density at the reference temperature.
8. Enter the Custom Liquid Viscosity at the given temperatures. Note that all
temperature values may be edited except the minimum and maximum
temperatures. The minimum and maximum values were set on the Fluid Selection
tab.
9. Proceed with the steps in Primary element selection.
Figure 2-17: Custom Liquid (Density [T]) Fluid Properties Tab
2.5 Basic device configuration
Mass and energy flow Fast Keys 1, 3
Direct process variable output Fast Keys 1, 3
This section provides procedures for configuring the basic requirements to commission
the Rosemount 3051SMV. The Basic Setup tab, shown in Figure 2-18, can be used to
perform all of the required transmitter configuration. The complete list of Field
Communicator Fast Keys for basic setup are shown in Field Communicator Fast Keys.
Reference Manual Configuration
00809-0100-4803 October 2018
Emerson.com/Rosemount 31