Position the security switch to the ( ) position to prevent accidental or deliberate change
of configuration data during normal operation.
6.4 Configuring in SIS applications
Use any HART capable configuration tool to communicate with and verify configuration of
the Rosemount 3051SMV.
Note
Transmitter output is not safety-rated during the following: configuration changes,
multidrop, and loop test. Alternative means should be used to ensure process safety
during transmitter configuration and maintenance activities.
6.4.1
Damping
User-selected damping will affect the transmitters ability to respond to changes in the
applied process. The damping value + response time must not exceed the loop
requirements.
Reference Damping to change damping value.
6.4.2
Alarm and saturation levels
DCS or safety logic solver should be configured to match transmitter configuration. Figure
6-1 identifies the three alarm levels available and their operation values.
Figure 6-1: Alarm Levels
Rosemount alarm level
Namur alarm level
Custom alarm level
Safety Instrumented Systems Requirements Reference Manual
October 2018 00809-0100-4803
144 Rosemount 3051S Multivariable Transmitter

Other manuals for Emerson Rosemount 3051S MultiVariable

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Rosemount 3051S MultiVariable and is the answer not in the manual?

Emerson Rosemount 3051S MultiVariable Specifications

General IconGeneral
Accuracy±0.04% of span
Pressure RangeUp to 4000 psi (276 bar)
Communication ProtocolsHART, FOUNDATION Fieldbus, PROFIBUS PA
Ambient Temperature Limit-40 to 85 °C (-40 to 185 °F)
Power Supply (Fieldbus)9-32 VDC
Measurement TypeTemperature, Flow
Output4-20 mA HART, FOUNDATION Fieldbus
Temperature Range-40 to 85°C (-40 to 185°F)
Material316L SST, Hastelloy, Monel
ServiceLiquid, gas, steam
Warranty5 years
Measurement Range0-4000 psi
Process Temperature Limit-40 to 120°C (-40 to 248°F)
DiagnosticsAdvanced diagnostics
Certifications/ApprovalsFM, CSA, ATEX, IECEx, SIL 2/3
Process Connection1/2-14 NPT
Electrical Connection1/2-14 NPT, M20
Enclosure RatingIP66, NEMA 4X
Stability±0.1% of URL per 5 years