Position the security switch to the ( ) position to prevent accidental or deliberate change
of configuration data during normal operation.
6.4 Configuring in SIS applications
Use any HART capable configuration tool to communicate with and verify configuration of
the Rosemount 3051SMV.
Note
Transmitter output is not safety-rated during the following: configuration changes,
multidrop, and loop test. Alternative means should be used to ensure process safety
during transmitter configuration and maintenance activities.
6.4.1
Damping
User-selected damping will affect the transmitters ability to respond to changes in the
applied process. The damping value + response time must not exceed the loop
requirements.
Reference Damping to change damping value.
6.4.2
Alarm and saturation levels
DCS or safety logic solver should be configured to match transmitter configuration. Figure
6-1 identifies the three alarm levels available and their operation values.
Figure 6-1: Alarm Levels
Rosemount alarm level
Namur alarm level
Custom alarm level
Safety Instrumented Systems Requirements Reference Manual
October 2018 00809-0100-4803