2 Configuration
2.1 Overview
This section contains information for configuring the flow and device configuration for the
Rosemount
™
3051S MultiVariable
™
Transmitter (Rosemount 3051SMV). Engineering
Assistant installation and Flow configuration instructions apply to Engineering Assistant
version 6.3 or later. Basic device configuration, Detailed device configuration , and
Variable configuration are shown for AMS Device Manager version 9.0 or later, but also
include Fast Key sequences for Field Communicator version 2.0 or later. Engineering
Assistant and AMS Device Manager screens are similar and follow the same instructions for
use and navigation. For convenience, Field Communicator Fast Key sequences are labeled
“Fast Keys” for each software function below the appropriate headings. The functionality
of each host as show in Table 2-1:
Note
Coplanar transmitter configurations measuring gage pressure and process temperature
(measurement 5) will report as the pressure as differential pressure. This will be reflected
on the LCD display, nameplate, digital interfaces, and other user interfaces.
Table 2-1: Host Functionality
• Available — Not available
Multivariable
type
Functionality Rosemount 3051SMV
Engineering Assistant
AMS Device
Manager
Field Communicator
Fully
compensated
mass and energy
flow (M)
Flow Configuration • • —
Device Configuration • • •
Test Calculation • • •
Calibration • • •
Diagnostics • • •
Direct process
variable output
(P)
Device Configuration — • •
Calibration — • •
Diagnostics — • •
2.2 Unresolved topicref
Unresolved topicref placeholder.
This is a placeholder for unresolved topicref links.
Reference Manual Configuration
00809-0100-4803 October 2018
Emerson.com/Rosemount 9