Section 3: HART commissioning
April 2014
HART® commissioning
5. Select the sensor for which Thermocouple Diagnostic will be disabled. Choose from 1
Sensor 1 or 2 Sensor 2 and press ENTER.
6. Select 2 Disable to disable Thermocouple Diagnostic and press ENTER.
7. Thermocouple Degradation has been disabled for the selected sensor. Press OK.