27
Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Installation
Option 3
1. Ground the sensor wiring shield at the sensor, if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the
transmitter housing and other fixtures that may be grounded.
3. Ground the signal wiring shield at the power supply end.
Grounded thermocouple inputs
1. Ground the sensor wiring shield at the sensor.
2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the
transmitter housing and other fixtures that may be grounded.
3. Ground the signal wiring shield at the power supply end.
Transmitter housing
Ground the transmitter housing according to local or site electrical requirements. An internal
ground terminal is standard. An optional external ground lug assembly (Option Code G1) can
also be ordered, if needed. Ordering certain hazardous approvals automatically includes an
external ground lug (see Table A-3 on page 206).
A. Sensor Wires C. 4-20 mA loop E. DCS
B. Transmitter D. Shield ground point
A. Sensor Wires C. 4-20 mA loop E. DCS
B. Transmitter D. Shield ground point
A
B
D
C
E
D
A
B
D
C
E
D