Reference Manual
00809-0100-4021, Rev GC
Section 6: Certified Safety Instrumented System (Safety-Certified)
April 2014
Certified safety instrumented system (safety-certified)
6.12.2 Inspection
The 3144P is repairable by major component replacement.
Visual inspection
Not required
Special tools
Not required
Product repair
All failures detected by the transmitter diagnostics or by the proof-test
must be reported. Feedback can be submitted electronically at http://www.emersonpro-
cess.com/rosemount/safety/safetyCertTemp.htm (Contact Us button).
6.13 Specifications
The 3144P must be operated according to the functional and performance specifications
provided in the 3144P Product Data Sheet (Document No. 00813-0100-4021) or in Appendix A:
Reference data.
6.13.1 Failure rate data
The FMEDA report includes failure rates, common cause Beta factor estimates, and independent
information on generic sensor models.
The report is available at http://www.emersonprocess.com/rosemount/safety/safetyCertTemp.htm
6.13.2 Product life
50 years – based on worst case component wear-out mechanisms – not based on wear-out of
process sensors.
Report any safety related product information at http://www.emersonprocess.com/rose-
mount/safety/safetyCertTemp.htm
6.14 Spare parts
This spare part is available for the 3144P Temperature Transmitter.
Description Part number
Safety Certified electronics module assembly 03144-3111-1007