Section 3: HART commissioning
April 2014
HART® commissioning
Resetting Active Sensor Drift Alerts: Fast Keys 1-1-1
1. Select 1 Overview.
2. Select 1 Device Status: (Maintenance or Failed).
3. Select 1 Refresh Alerts.
3.8 Device output configuration
Device output configuration contains PV range values, alarm and saturation, HART output, and
LCD display options.
3.8.1 PV range values
Field communicator
The PV URV and PV LRV commands, found in the PV Range Values menu screen, allow the user to
set the transmitter’s lower and upper range values using limits of expected readings. See Tab le
A-1 on page 196 for unit and range setting limits. The range of expected readings is defined by
the Lower Range Value (LRV) and Upper Range Value (URV). The transmitter range values may
be reset as often as necessary to reflect changing process conditions. From the PV Range Values
screen select 1 PV LRV to change the lower range value and 2 PV URV to change the upper range
value.
HART 5 Fast Keys
2, 2, 5, 5
HART 7 Fast Keys
2, 2, 5, 5