EasyManua.ls Logo

Emerson Rosemount - Recommended Actions for Field Diagnostics Per NE107; Resource Block Diagnostics

Emerson Rosemount
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
149
Reference Manual
00809-0100-4021, Rev GC
Section 4: FOUNDATION fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
4.5.4 Recommended actions for field diagnostics per NE107
4.5.5 Resource block diagnostics
Block errors
Table 4-3 lists conditions reported in the BLOCK_ERR parameter.
Alarm type Active event name Recommended Action text string
Maintenance Required Diagnostic Error Device sensor diagnostic has been triggered
Process Anomoly Detected N/A
Out of Specification Configuration Error Re-write the Sensor Configuration
Primary Value Degraded Confirm the operating range of the applied
sensor and/or verify the sensor connection
and device environment
Calibration Error Retrim the device
Secondary Value Degraded Verify the ambient temperature is within
operating limits
Failed Electronics Failure Replace the Device
Asic Failure Replace the Device
HW / SW Incompatible Verify the Hardware Revision is compatible
with the Software Revision
NV Memory Failure Reset the device then download the Device
Configuration
Primary Value Failure Verify the instrument process is within the
Sensor range and/or confirm sensor
configuration and wiring
Secondary Value Failure Verify sensor range and/or confirm sensor
configuration and wiring
Function Check Check Transducer Block is under maintenance
Table 4-3. Resource Block BLOCK_ERR messages
Condition name and description
Other
Device Needs Maintenance Now
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost
Device Needs Maintenance Now
Out of Service: The actual mode is out of service

Table of Contents