EasyManua.ls Logo

Emerson Rosemount - 6.7 Certification; 6.8 3144 P safety-certified identification; 6.9 Installation; 6.10 Commissioning

Emerson Rosemount
252 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
171
Reference Manual
00809-0100-4021, Rev GC
Section 4: FOUNDATION fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
4.11.1 FOUNDATION fieldbus
If a malfunction is suspected despite the absence of a diagnostics message, follow the
procedures described in Table 4-12 to verify that transmitter hardware and process connections
are in good working order. Under each of the symptoms, specific suggestions for solving
problems are offered. Always deal with the most likely and easiest-to-check conditions first.
Table 4-12. F
OUNDATION fieldbus Troubleshooting
Symptom Potential source Corrective action
Transmitter does not
Communicate with the
Configuration Interface
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide
complete functionality
Check for intermittent wire shorts, open circuits, and multiple grounds.
Network
parameters
•See “Failure mode switch” on page 188.
High Output Sensor Input
Failure or
Connection
Enter the transmitter test mode to isolate a sensor failure.
Check for a sensor open circuit.
Check the process variable to see if it is out of range.
Loop Wiring
Check for dirty or defective terminals, interconnecting pins, or
receptacles.
Electronics Module
Enter the transmitter test mode to isolate a module failure.
Check the sensor limits to ensure calibration adjustments are within the
sensor range.
Erratic Output Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide
complete functionality.
Check for intermittent wire shorts, open circuits, and multiple grounds.
Electronics Module
Enter the transmitter test mode to isolate module failure.
Low Output or No
Output
Sensor Element
Enter the transmitter test mode to isolate a sensor failure.
Check the process variable to see if it is out of range.
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide
complete functionality.
Check for wire shorts and multiple grounds.
Check the loop impedance.
Check wire insulation to detect possible shorts to ground.
Electronics Module
Check the sensor limits to ensure calibration adjustments are within the
sensor range.
Enter the transmitter test mode to isolate an electronics module failure.

Table of Contents

Other manuals for Emerson Rosemount

Related product manuals