Section 4: FOUNDATION fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
Figure 4-3. Problems with communications flowchart
Communications established but have “Block_err” or an
“Alarm” Condition.
See “PlantWeb™ alerts” on page 145
Read the following parameters in the Resource Block to
determine the recommended action.
BLOCK_ERR (see Tab le )
SUMMARY_STATUS (see Table 4-4)
DETAILED_STATUS (see Table 4-4)
Perform Recommended
Action, see Table 4-4.
For more detailed
information
Perform the following steps in the Sensor Transducer Block
to determine the recommended action.
BLOCK_ERR (see Table 4-5)
XD_ERR (see Table 4-6)
DETAILED_STATUS (see Ta bl e )
RECOMMENDED_ACTION (see Ta bl e )
SENSOR_DETAILED STATUS (see Tab l e )
If error condition does not exist in
the Resource Block then it is a
configuration problem, see AI
BLOCK_ERR Conditions in Table 4-9
If the problem persists
contact your local Emerson
representative.
Perform Recommended
Action, see Ta b le .
Perform Recommended
Action, see Table 4-10.
Perform Recommended
Action, see Table 4-12 on
page 4-171.