126
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
HART® commissioning
Configure Transmitter Sensor Matching in guided setup
Note
The guided setup will take you through the complete sensor configuration. This document will
guide you through the specific Transmitter Sensor Matching section.
1. From the Home Screen, select 2 Configure.
2. Select 1 Guided Setup.
3. Select 1 Configure Sensors.
4. When prompted, choose 1 Configure Sensor 1. If you are using dual RTDs, you may
also choose 2 Configure Sensor 2, or 3 Configure Both Sensors the Same.