00809-0100-4021, Rev GC
Section 4: FOUNDATION fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
ADVISE_ENABLED
The ADVISE_ENABLED parameter contains a list of informative conditions that do not have a
direct impact on the device's primary functions. Below is a list of the advisories with the highest
priority first.
1. NV Writes Deferred
2. SPM Process Anomaly detected
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed in ADVISE_ENABLED.
A bit on means the condition is masked from alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see “Process alarms” on
page 159. The default is 0, and the recommended values are 1 or 2.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays the active advisories. Only the advisory with the
highest priority is displayed. This priority is not the same as the ADVISE_PRI parameter
described above, but is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM indicates advisory alarms. These conditions do not have a direct impact on the
process or device integrity.