12
Reference Manual
00809-0100-4021, Rev GC
Section 2: Installation
April 2014
Installation
FOUNDATION fieldbus
Without an LCD display
1. If the transmitter is installed in a loop, set the loop to Out-of-Service (OOS) mode (if
applicable) and disconnect the power.
2. Remove the housing cover on the electronics side of the transmitter. Do not remove
the transmitter cover in explosive atmospheres with a live circuit.
3. Set the switches to the desired position (see Figure 2-1).
4. Replace the transmitter cover. Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
5. Apply power and set the loop to In-Service mode.
With an LCD display
1. If the transmitter is installed in a loop, set the loop to OOS (if applicable) and disconnect
the power.
2. Remove the housing cover on the electronics side of the transmitter. Do not remove
the transmitter cover in explosive atmospheres with a live circuit.
3. Unscrew the LCD display screws and gently pull the meter straight off.
4. Set the switches to the desired position.
5. Replace and tighten the LCD display screws to secure the LCD display.
6. Replace the transmitter cover. Both transmitter covers must be fully engaged to meet
explosion-proof requirements.
7. Apply power and set the loop to In-Service mode.
Figure 2-2. Transmitter Switch Locations
Dimensions are in inches (millimeters).
A. Switches
(1)
B. LCD display connector
C. 4.4 (112)
D. 4.4 (112)
(1) Alarm and Security (HART), Simulate and Write Protect (FOUNDATION fieldbus)