PROCESS OUTPUTS
HEATING1 : 0%
HEATING2 : 0%
COOLING : 0%
HUMIDITY : 0%
TUNNEL VENT. : 0%00
SHUTTER : 0%00
LIGHTING ANALOG: 0%
HEATING1: HEATER 1 output value (Range: 0% - 100%).
HEATING2: HEATER 2 output value (Range: 0% - 100%).
COOLING: COOLING output value (Range: 0% - 100%).
HUMIDITY: HUMIDITY output value (Range: 0% - 100%).
VENTILATION: Ventilation output value (Range: 0%00 - 8%00).
SHUTTER: Shutter output value (Range: 0%00 - 8%00).
LIGHTING ANALOG: Lighting 0- 10 VZ output value (Range: 0% - 100%).
5.4.12 PROCESS OUTPUTS
MAX & MIN VALUES 1
HOUSE MIN : 0.0°C
TIME : 00.00
HOUSE MAX : 0.0°C
TIME : 00.00
HOUSE MIN: Minimum Temperature value of last 24 hours (NOTE 1).
TIME: Minimum Temperature value’s captured time (hour.minute) (NOTE 1).
HOUSE MAX: Maximum Temperature value of last 24 hours (NOTE 1).
TIME: Maximum Temperature value’s captured time (hour.minute) (NOTE 1).
OUTSIDE MIN: Minimum Temperature value of OUTSIDE of last 24 hours (NOTE 2).
TIME: Minimum Temperature value’s captured time (hour.minute) (NOTE 2).
OUTSIDE MAX: Maximum Temperature value of OUTSIDE of last 24 hours (NOTE 2).
TIME: Maximum Temperature value’s captured time (hour.minute) (NOTE 2).
5.4.13 MAX & MIN VALUES
NOTE 1: MAX & MIN VALUES 1 PAGE shows the saved minimum and maximum temperature values of
last 24 hours that was token from
ROOM1 or
ROOM2 or
(ROOM1 + ROOM2)/2
The selection depends on SELECT HOUSE SENSOR PAGE FOR MINMAX parameter.
- If sensor is broken then EPC keeps on showing last measured maximum and minimum temperatures.
- If SELECT HOUSE SENSOR PAGE FOR MINMAX parameter is ROOM1&2 and one of two sensors is
broken then EPC keeps on working by using other one.
- EPC will show nothing if using sensor or sensors are broken before energized EPC.
NOTE 2:MAX & MIN VALUES 1 PAGE shows the saved minimum and maximum temperature values of
last 24 hours that was token from OUTSIDE sensor.
- If outside sensor is broken then EPC keeps on showing last measured maximum and minimum
temperatures.
- EPC will show nothing, if outside sensor is broken before energized EPC.
MAX & MIN VALUES 2
OUTSIDE MIN: 0.0°C
TIME : 00.00
OUTSIDE MAX: 0.0°C
TIME : 00.00