ROOM1 OFFSET: Room1 Temperature Offset set value
(Range: -10.0 °C - 10.0 °C / Factory Setting: 0.0 °C).
ROOM2 OFFSET: Room2 Temperature Offset set value
(Range: -10.0 °C - 10.0 °C / Factory Setting: 0.0 °C).
OUTSIDE OFFSET: Outside Temperature Offset set value
(Range: -10.0 °C - 10.0 °C / Factory Setting: 0.0 °C).
HUMIDITY OFFSET: Humidity Offset set value
(Range: -20% - 20% / Factory Setting: 0%).
SENS MINMAX: Sensor selection for MAX & MIN VALUES 1 PAGE
(Range: ROOM1 - ROOM2- ROOM1&2 / Factory Setting: ROOM1&2).
MAX & MIN VALUES 1 PAGE shows the saved minimum and maximum temperature values of
last 24 hours that was token from
ROOM1 or ROOM2 or (ROOM1 + ROOM2)/2
The selection depends on TEMPERATURE SETTINGS PAGE SENS MINMAX parameter.
SENS OPENING: Sensor selection for PROCESS VALUES PAGE HOUSE parameter
(Range: ROOM1 - ROOM2- ROOM1&2 / Factory Setting: ROOM1&2).
PROCESS VALUES PAGE HOUSE parameter shows temperature value from
ROOM1 or ROOM2 or (ROOM1 + ROOM2)/2
The selection depends on TEMPERATURE SETTINGS PAGE SENS OPENING parameter.
TEMPERATURE SETTINGS
ROOM1 OFFSET: 0.0°C
ROOM2 OFFSET: 0.0°C
OUT. OFFSET : 0.0°C
HUM. OFFSET : 0%
SENS MINMAX : ROOM1&2
SENS OPENING: ROOM1&2
6.4.8 TEMPERATURE SETTINGS
62
6.4.7 SHUTTER CALIBRATION(EPC1A,EPC3A,EPC4A)
SHUTTER CALIBRATION
SHUTTER CLOSE: NO
SHUTTER OPEN: NO
1000
If SHUTTER PARAMETERS PAGE SHUT.FEEDB. parameter is ENABLE this page is shown. When calibrating shutter
firstly push MAN/AUTO button to manually control the shutter. Press DOWN button to close the shutter. When the shutter
fully closed select SHUTTER CLOSE parameter and change this parameter to YES. Wait for the parameter value to
turn NO. After this press UP button to open the shutter. When the shutter fully opened select SHUTTER OPEN parameter
and change this parameter to YES. Wait for the parameter value to turn NO and 1000 value seen on the screen.
SHUTTER PARAMETERS
STROKE TIME: 100SEC
STEP : 0.1%
SHUT.FEEDB.: DISABLE
STROKE TIME: Stroke time set value (Range: 5 SEC- 600 SEC / Factory Setting: 100 SEC)
STEP: Stroke time step set value (Range: 0.1% - 5.0% / Factory Setting: 0.1% )
SHUT.FEEDB.: Shutter feedback function(disable,enable)