VENTIL. PARAMETERS
SHIFTING : ON
SHIFT&PRP PER: 10MIN
FAN MIN TIME : 5SEC
PRPRTN RAMP : 50SEC
SENSOR : ROOM1
FAN CONT.: BASIC&TUN.
FAN COUNT BAS:1 TOT:8
SHIFTING: Shift enabled or disabled or without chimney fans. (Range: OFF - CMN / Factory Setting: ON).
SHIFT&PRP PER: Common set period value for proportion and shifting
(Range: 1 MIN - 100 MIN / Factory Setting: 2 MIN).
FAN MIN TIME: Mýnýmum on time & Minimum off time (Range: 0 SEC - 100 SEC / Factory Setting: 5 SEC).
PRPRTN RAMP: Proportion ramp set value (Range: 0 SEC - 999 SEC / Factory Setting: 0 SEC).
SENSOR: Sensor selection set value
(Range: ROOM1, ROOM2, ROOM1&2 / Factory Setting: ROOM1&2).
FAN CONT: Ventilation type selection. (Range: TUNNEL, BASIC&TUN. / Factory Setting:TUNNEL)
FAN COUNT BAS: Fan count that run at minimum ventilation. (Range: 1 - 7 / Factory Setting: 1)
FAN COUNT TOT: Total fan count. (Range: 1 - 8 / Factory Setting: 8)
6.4.6.1 VENTILATION PARAMETERS
SET VENTILATION<°C>
VENT1: 0.5 VENT5: 2.5
VENT2: 1.0 VENT6: 3.0
VENT3: 1.5 VENT7: 3.5
VENT4: 2.0 VENT8: 4.0
F.HYS: 0.2 WAIT : 1
FAN ANALOG: BASIC
VENT ALG. :PROPORTION
VENT1: Ventilation stage 1 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 0.5 °C).
VENT2: Ventilation stage 2 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 1.0 °C).
VENT3: Ventilation stage 3 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 1.5 °C).
VENT4: Ventilation stage 4 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 2.0 °C).
VENT5: Ventilation stage 5 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 2.5 °C).
VENT6: Ventilation stage 6 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 3.0 °C).
VENT7: Ventilation stage 7 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 3.5 °C).
VENT8: Ventilation stage 8 set value (Range: 0.0 °C - 50.0 °C / Factory Setting: 4.0 °C).
F.HYS: Fans hysterisis value(Range: 0.0 °C - 5.0 °C / Factory Setting: 0.2 °C).
WAIT: Delay time before fans (Range: 0.0 °C - 200 Sec. / Factory Setting: 1 Sec).
FAN ANALOG: Fan Analog output operation section
(Range: TUNNEL, BASIC&TUN. / Factory Setting:TUNNEL).
VENT ALG.: Working algorithm of fans.
(Range: ON/OFF, PROPORTION / Factory Setting:ON/OFF).
6.4.6.2 SET VENTILATION <°C>°C>