If CONTROL FUNC PAGE 2 PAGE LIGHT CONT parameter is equal to
MODULATE then working princible is explained below;
- First of all EPC has to capture START TIME to run a step.
- If OUT% is 0 then relay output is OFF otherwise relay output is ON
See the example;
Working without curve:
Next page parameters are used :
Working with curve:
- SET VALUES PAGE DAY < CURVE STEP2 DAY, LIGHTING PARAMETERS PAGE step1 parameters are
used,
- CURVE STEP2 DAY<=SET VALUES PAGE DAY < CURVE STEP3 DAY, LIGHTING PARAMETERS PAGE
step2 parameters are used,
- CURVE STEP3 DAY<=SET VALUES PAGE DAY < CURVE STEP4 DAY, LIGHTING PARAMETERS PAGE
step3 parameters are used,
- CURVE STEP4 DAY<=SET VALUES PAGE DAY < CURVE STEP5 DAY, LIGHTING PARAMETERS PAGE
step4 parameters are used,
- CURVE STEP5 DAY<=SET VALUES PAGE DAY < CURVE STEP6 DAY, LIGHTING PARAMETERS PAGE
step5 parameters are used,
- CURVE STEP6 DAY<=SET VALUES PAGE DAY < CURVE STEP7 DAY, LIGHTING PARAMETERS PAGE
step6 parameters are used,
- CURVE STEP7 DAY<=SET VALUES PAGE DAY < CURVE STEP8 DAY, LIGHTING PARAMETERS PAGE
step7 parameters are used,
- CURVE STEP8 DAY<=SET VALUES PAGE DAY < CURVE STEP9 DAY, LIGHTING PARAMETERS PAGE
step8 parameters are used,
- CURVE STEP9 DAY<=SET VALUES PAGE DAY < CURVE STEP10 DAY, LIGHTING PARAMETERS PAGE
step9 parameters are used,
- CURVE STEP10 DAY<=SET VALUES PAGE DAY, LIGHTING PARAMETERS PAGE step10 parameters are
used.
LIGHTING PARAMETERS
CURVE STEP X
L1: 00:00 00:00 0%
L2: 00:00 00:00 0%
L3: 00:00 00:00 0%
L4: 00:00 00:00 0%
L5: 00:00 00:00 0%
HR:MN HR:MN OUT%
100
0
Time[HR:MN]
02:00
01:00
01:30
02:00
20
40
50
LIGHTING ANALOG
OUTPUT[%]
04:00 07:00 08:30 16:00 21:0000:00
CONTROL FUNC PAGE 2
FEEDING : ENABLE
CHICKS W1 : ENABLE
CHICKS W2 : ENABLE
CHICKS W3 : ENABLE
LIGHTING : ENABLE
LIGHT CONT: MODULATE
LIGHTING PARAMETERS
L1: 04:00 02:00 20%
L2: 07:00 01:00 40%
L3: 08:30 01:30 50%
L4: 16:00 00:00 0%
L5: 21:00 02:00 100%
HR:MN HR:MN OUT%
2.0 Vdc & relay is on
4.0 Vdc & relay is on
5.0 Vdc & relay is on
0.0 Vdc & relay is off
10.0 Vdc & relay is on
Start time column
Duration column
LIGHTING PARAMETERS
L1: 04:00 02:00 20%
L2: 07:00 01:00 40%
L3: 08:30 01:30 50%
L4: 16:00 00:00 0%
L5: 21:00 02:00 100%
HR:MN HR:MN OUT%
ON
OFF
Time[HR:MN]
02:00
04:00 07:00
01:00
08:30
01:30
16:00 21:0000:00
02:00
Relay
Output
6.4.11.2 LIGHTING (MODULATE MODE) FUNCTION (EPC 3&4)
65