ENGINE SPEED SETS (Engine->Speed settings)
Max
Engine Under Speed Shutdown
Engine Under Speed Prealarm
Engine Under Speed Prealarm Reset
dis
Engine Over Speed Shutdown
500(dis) 5000
500(dis)
RPM
500
500 5000
Engine Over Speed Prealarm Reset
Engine Speed Shutdown Delay Time
500
1.0
RPM
RPM
RPM
RPM
RPM
Sec
5000
500(dis) 5000
5000
5000
10.0
Engine Over Speed Prealarm
Under speed shutdown
Under speed prealarm
Under speed reset
Over speed shutdown
Over speed prealarm
Over speed reset
Shutdown delay time
500
0.0
The parameters in this page are used for the generator speed low and high alarms.
36
Note: dis = disable
The parameters in this page are used for engine started signals. If any of the selected signals appears,
the unit assumes that the engine has started.
If the generator frequency over than 30.0 Hz, the unit assumes that the engine has started and the unit
stop cranking.
If the generator speed over than 500 Rpm, the unit assumes that the engine has started and the unit
stop cranking.
If the generator voltage over than 300 Vac, the unit assumes that the engine has started and the unit
stop cranking.
If the charge alternator voltage over than 6.1 Vdc, the unit assumes that the engine has started and
the unit stop cranking. Note: If the charge generator input (terminal #35) is disconnect, this parameter
selected as disabled (6.0 Vdc).
This parameter is used for to activate of the crank disconnect on oil pressure feature.
If the oil pressure sender over than this value, the unit assumes that the engine has started and the
unit stop cranking.
If this parameter is enabled, the unit will not be allowed to crank if the oil pressure isn’t seen as being
low.
Crank Disconnect On Gen. Frequency
Crank Disconnect On Engine RPM
Crank Disconnect On Gen. Voltage
Crank Disconnect On Charge Alt. Voltage
Crank Disconnect On Oil Pressure En/Dis
Oil Pressure Value
Check Oil Pressure Before Start
Nominal Speed
1500
500 5000
RPM
Nominal speed
dis
dis
dis
500(dis)
ENG. CRANK DISCONNECT (Engine->Crank disconnect)
Generator frequency
Engine speed
Generator volt
Charge alt. volt
Oil pres. enab./dis.
Oil pressure value
Check oil befor.start
Min
Default
UnitMax
Crank Disconnect On Gen. Frequency
Crank Disconnect On Gen. Voltage
Crank Disconnect On Charge Alt. Voltage
30.0
Crank Disconnect On Oil Pressure En/Dis
Oil Pressure Value
Check Oil Pressure Before Start
10.0 75.0
Hz
500
100 6000
RPM
300
60 (dis) 600
VV
dis
6.0 (dis) 30.0
VZ
1.0 30.0
BAR
Crank Disconnect On Engine RPM
1.0
ENABL/DISBL DISBL
ENABL/DISBL ENABL